- DMTECH
- Conventional fire alarm panel of 8 zones
- Certificate EN54-2 and EN54-4
- 2 independent siren outputs
- 2 auxiliary alarm and fault outputs
- 2 configurable relay outputs
- Individual output for repeaters
- Capacity for 2 12V batteries
- 4 access levels ((3 user and 1 manufacturer)
- LCD display with menu for advanced programming
DMT-FP9000-8-EN
Conventional central 8 areas with LCD screen2 Siren output2 alarm and fault outputs and 2 configurable relay outputsRepeater outputUp to 30 detectors per zoneEnd-of-line resistance auto detection
1.360,37 kr.
Our courier will deliver to the specified address
5-12 Days
150 kr
Our courier will deliver to the specified address
2-4 Days
300 kr
Description
Specification
Overview
Primary power supply |
Switching source 187-252V AC 50-60 Hz 65W max. |
---|---|
Backup power supply |
2 batteries 12VDC (up to 5 Ah). Ensures minimum 72 hours duration. |
Available languages |
Spanish, English, Portuguese, Italian, French, and German. |
Number of zones |
8 zones, up to 30 detectors by area. |
Siren outputs |
2 siren outputs 24VDC. Independent and monitored open collector outputs |
Relay outputs |
4 Relay outputs: [VAR%] Alarm output, 1 Fault output and 1 configurable relay outputs. All support 30VDC 3A max. |
End of line resistance |
Areas fully monitored by end-of-line resistance (4.7K) |
Auxiliary Output Voltage |
24VDC. Protected by resettable electronic fuse 1.85A |
Protection Index |
IP30 |
Temperature |
-5ºC~+45ºC |
Material and colour |
ABS, colour: White |
Dimensions |
310 x 240 x 80 mm |
Weight |
1,3Kg |
Recommended cable |
Fire cable with a minimum section of 1.0mm (18AWG). |